Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Ympäristötalo, construction year 2011
Construction management | City of Helsinki, PWD-Construction Management (HKR-Rakennuttaja) |
Owner | City of Helsinki, Environment Centre |
Construction costs | 16.5 million € (2 430 €/m²) |
Estimated nZEB extra construction cost | 0.5–0.7 million € (70–100 €/m², 3-4 %) |
Heated net floor area | 6 390 m² |
Gross floor area | 6 791 m² |
Occupants/ mean occupant density | 240 / 25 m²/person (overall average) |
Architect | Ab Case Consult Ltd, Kimmo Kuismanen |
HVAC-design | ClimaConsult Finland |
Technical data
OUTDOOR
CLIMATE DATA: | |
Design outdoor temperature for heating | -26°C |
Design outdoor temperature and RH for cooling | 28°C / 50% |
Heating degree days (base temperature 17°C) | 3 952 degree days |
INDOOR
ENVIRONMENTAL QUALITY TARGETS: | |
Indoor air quality | |
Air flow rate, offices | 1.5 l/s per m² |
Air flow rate, meeting rooms | 4 l/s per m² |
Thermal environment | |
Indoor temperature, heating season | 21°C |
Indoor temperature, cooling season | 25°C |
Air velocity, winter | 0.14 m/s |
Air velocity, summer | 0.20 m/s |
Lighting | |
Illuminance level | 300/500 lx. |
Building envelope: | |
Window U-value | 0.8 W/(m²K) |
Window g-value | 0.3 |
Exterior wall U-value | 0.17 W/(m²K) |
Base floor U-value | 0.16 W/(m²K) |
Roof U-value | 0.09 W/(m²K) |
Average U-value of the building envelope | 0.259 W/(m²K) |
Specific heat loss per net floor area H/A | 0.276 W/(K m²) |
Air leakage rate at 50 Pa | 0.56 ach |
The building has a high quality building envelope, south facades being double facades with integrated PV cells providing effective solar protection at the same time. All the building, except the atrium space, is air-conditioned with effective integrated balanced ventilation and free cooling system with passive and active chilled beams. All the cooling is from boreholes, which water is directly circulated in air handling units and chilled beams. Heating systems is based on district heating and water radiators. Highly significant energy efficiency measures are large air handling units and ductworks enabling low specific fan power, combined with demand controlled ventilation in most of rooms except cellular offices, and effectively controlled lighting. The simulated energy performance is shown in Table 1. On site renewable energy production of 7.1 kWh/(m² a) PV power generation and 10.6 kWh/(m² a) free cooling from boreholes have significant effect on achieved total primary energy value of 85 kWh/(m² a). Typical to nZEB buildings, the highest primary energy component is the small power loads.
Table 1. Simulated energy performance (all values per net floor area).
Net
energy | Delivered | Energy | Primary | |
Space and ventilation heating | 26.6 | 32.2 | 0.7 | 22.6 |
Hot water heating | 4.7 | 6.1 | 0.7 | 4.3 |
Cooling | 10.6 | 0.3 | 1.7 | 0.5 |
Fans and pumps | 9.4 | 9.4 | 1.7 | 16.0 |
Lighting | 12.5 | 12.5 | 1.7 | 21.3 |
Appliances (plug loads) | 19.3 | 19.3 | 1.7 | 32.7 |
PV | -7.1 | 1.7 | -12.0 | |
Total | 83 | 73 | 85 |
The building has a reasonable compact massing and excessive glazed areas are avoided. The main facade to south is accomplished as a double facade in order to provide effective solar shading and to serve as mounting for PV panels. Window area is 23% of the external wall area, but the double main facade still provides an outlook of a glass building from major direction. The double facade is open from bottom and has motorized ventilation openings on the top. In total there are about 30 motorized openings/windows used for the double facade and atrium excess heat removal and some of them are also used for smoke removal. The openings are to be open when needed (manual control from reception) and they will be closed by weather station control, based on wind, rain and temperature, automatically.
Windows have blinds between panes.
The building is connected to Helsinki district
heating system. District heating is used for hot water and space heating
through central air handling units and hot water radiators.
All cooling need is covered with free cooling from borehole water. The borehole system consists of 25 boreholes each 250 m deep. A simple borehole cooling system with a circulation pump and a water tank serves both the central air handling units and chilled beam units installed in offices and other spaces. Boreholes are sized to provide 15°C supply design temperature (return 20°C) to the water tank at dimensioning conditions (normally the borehole water temperature is lower). Air handling units’ cooling coils and chilled beams network are sized to 16/20°C design flow temperatures from this water tank.
South facade of the building has a double facade with vertical PV panels and some panels are also installed on the roof. The total installed PV power is 60 kW (570 m²) that provides about 17% of electricity use of the building.
PV installation on the double facade to south serving also as an effective solar shading.
The building has an air-conditioning system with mechanical supply and exhaust ventilation and chilled beams. There are 3 main air handling units and 4 risers with zone dampers for each floor. Separated exhaust fans for toilets are not used and are replaced with a small 0.5 m³/s air handling unit with rotary heat exchanger. The main large air handling units of 2.4, 4.2 and 4.0 m³/s have heat recovery temperature ratios of 80, 79 and 78% respectively. The rest, smaller air handling units have temperature ratios of 80–81%. Ventilation system is balanced so that design supply air flows equal to design extract air flows.
Outdoor air is filtered and heated or cooled in central air handling units and supplied to rooms. Supply air is heated in the central air handling units partly with heat recovered from extract air and partly with heating coils. When cooling is needed, supply air is first cooled in the central air handling units and then cooled further in the chilled beam units.
Air conditioning system with mechanical supply and exhaust ventilation and chilled beams.
Atrium space of the building has no installed cooling and overheating is avoided by opening bottom and top windows. Motorized openable widows are to be open manually when needed and will be closed by weather station control (wind, rain and temperature control) automatically.
Large air handling units and ductworks have been used to achieve as low specific fan power as 1.4–1.6 kW/(m3/s) for offices and similar spaces and 1.8 kW/(m3/s) for VAV air handling unit serving meeting rooms.
All open-plan and cellular office spaces have room
conditioning with active or passive chilled beam units installed in the
ceiling, and controlled by room temperature controllers. Air volume flow rate
is kept constant (constant pressure
Active chilled beams are used in cellular offices and passive chilled beams in other rooms. Passive chilled beams allow to use cooling also during nights and weekends when ventilation is switched off. This reduces peak cooling loads to 40W/m² that is important in the free cooling system with limited capacity.
Ventilation in the meeting rooms, lobby and
workshop areas is controlled by CO2 and temperature sensors. VAV
dampers are used and air flow rates in the meeting rooms are controlled between
0–4 l/(s m²). Office rooms have CAV ventilation of 1.5 l/(s m²).
The major part of cooling and heating is supplied by the water systems (beams
and radiators respectively).
Active chilled beams and lighting fittings in
offices.
Supply air temperature is extract air temperature compensated and is set between 17 to 22°C. The supply air temperature is controlled by adjusting the rotation speed of the regenerative heat exchanger and the water flow control valves of the heating and cooling coils.
Lighting systems uses lighting fittings of
T5 fluorescent lamps with 7 W/m² installed power. Daylight, occupancy and
time control is used in larger rooms, and occupancy and time control in cellular
offices. Lights and chilled beam units have a communication link to building
management system (
The best energy performance of an office building ever built in Finland. Total primary energy use of 85 kWh/(m² a) including small power loads is an half of a code requirement of 170 kWh/(m² a) and is expected to comply with future nearly zero energy building requirement.
Very good indoor climate quality according to Finnish Classification of Indoor Environment.
Well controlled construction cost of 2 430 €/m² is roughly a cost for standard office building in Finland, including only 3...4% extra energy performance related cost.
Follow us on social media accounts to stay up to date with REHVA actualities
0