Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
|
|
|
|
Alireza Afshari | Göran Hultmark | Haider Latif | Alessandro Maccarini | Samira Rahnama |
Department of the Built Environment (BUILD), Aalborg University Copenhagen, Denmark | ||||
Optimal thermal comfort significantly impacts the well-being and productivity of office occupants [1, 2]. In open-plan offices, the need for individualized control over environmental factors, such as air velocity and temperature, is frequently emphasized [3, 4].
Thermal comfort results from the interplay of personal and environmental factors. Personal factors include variables like metabolic rates (such as muscle mass, diet, health, age, gender, and activity) as well as clothing insulation, while environmental factors encompass air speed, air temperature, radiant temperature, and humidity [5]. Environmental factors wield substantial influence over personal factors, ultimately determining the comfort or discomfort experienced by office occupants [6]. Following the ISO 7730 Standard, a seated office occupant typically sustains a metabolic rate (MET) of 1.2 MET [7], yet this metric can fluctuate based on personal factors [8, 9].
Conventional mixing ventilation systems fall short of achieving personalized thermal comfort, as uniform conditions fail to satisfy individual requirements. This holds true even for traditional ACB systems lacking JetCones, as they mix cold supply air with warmer room air to achieve thermal consistency [10]. Precision Ventilation builds upon the foundation of a conventional mixing ventilation system. However, it innovatively introduces adjustable air patterns in various directions, thereby crafting an environment of personalized thermal comfort.
In contrast, over the past two decades, traditional personalized ventilation systems have been employed within office settings to establish micro-climates around workstations. These systems utilize various Air Terminal Devices to control airflow rates, directions, and temperatures, resulting in localized thermal comfort conditions and substantial energy conservation [11-13]. Some studies have even utilized more than five Air Terminal Devices around a single workstation to ensure precise localized thermal comfort [14, 15]. By elevating the cooling setpoint temperature of the room to as high as 30°C, traditional personalized ventilation systems have exhibited remarkable energy savings, reaching up to 60% [16-18]. While these systems indeed offer significant energy benefits, their implementation necessitates the incorporation of multiple dimensionally modified Air Terminal Devices to establish micro-climates around office workstations [19].
To address the complexity associated with multiple Air Terminal Devices, a modified ventilation strategy is required, one that can establish micro-climate zones without necessitating alterations to the existing office layout. Precision Ventilation [20, 21] emerges as a technique tailored to meet the specific thermal comfort needs of occupants in open-plan offices. This method entails the strategic positioning of high or low-velocity supply jets, effectively creating distinct air velocity zones within the communal office area. Through the integration of JetCones in ACBs, airflow regulation becomes feasible, enabling personalized airflow distribution in alignment with the relevant metabolic rates for each designated zone [22].
Air velocity is one of the most crucial controllable parameters that influence the convective heat transfer between the human body and the surrounding environment [23, 24]. Among building designers, the energy demand perspective has changed and has resulted in an increase in the temperature setpoint to certain degrees [25]. This has left users to increase the room air velocities to compensate for warm room temperatures. This shift of negative discomfort caused by draught to the positive benefits of achieving acceptable thermal comfort by raising air velocities in warm indoor climates has been achieved in various studies as shown in Table 1.
Table 1. Studies with elevated air temperatures and air velocities.
References | Air velocity limit | Room temperature limit |
[26] | 1 m/s | 29°C |
[27] | 1 m/s | 28°C |
[12] | 1.4 m/s | 29°C |
[28-30] | 1 – 1.5 m/s | Up to 31°C |
[31] | 1.6 m/s | 31°C |
As per the EN ISO 7730 Standard [32], a connection exists between air velocities and elevated air temperatures to attain a satisfactory comfort level for occupants, see Figure 1.

Figure 1. Air velocities required for a temperature rise above 26°C. [7, 32]
The experiments involved ACBs equipped with JetCones, designed to effectively manage airflow in various directions through the use of adjustable regulators, as illustrated in Figure 2. The inherent JetCone functionality integrated into the ACBs offers a versatile means of altering supply airflow patterns. The adjustment regulators are marked with numbers ranging from 0 to 9. Each ACB's JetCones can be managed using four adjustment regulators, with the highest airflow achieved when JetCones are positioned at 9 and the lowest airflow at 0, see Figure 3. This Precision Ventilation is attained by maintaining a consistent total airflow from the system, all the while creating zones of varying air velocity through the adjustment of JetCones. These JetCones can be fine-tuned either manually or continuously through actuators, rendering Precision Ventilation a fully operational Demand Controlled Ventilation (DCV) System.
Experiments were carried out utilizing varying quantities of ACBs to define distinct air velocity zones tailored to the specific metabolic requirements of occupants. The air temperature emitted by the ACB is cooler by 3.5°C compared to the ambient room temperature, indicative of a heat load approximately around 25 W/m².


Figure 2. Experimental setup.

Figure 3. Air pattern out of the ACB.
The test room's geometry was replicated in SolidWorks 2020 software, mirroring the exact dimensions of the real setup, as depicted in Figure 4. The simulated ACB geometry took on a circular form and was partitioned into 16 segments, resulting in radial airflow emanating from the ACB. The air velocities at 16 specific points on the ACB inlets, measured through experimentation, were applied as inlet air velocities for the radial ACB configuration, as illustrated in Figure 4. To ensure greater accuracy in dealing with mixed conventional airflows and enhance robustness, the RNG k-ε turbulence model was selected for the numerical simulations, following a successful grid independence test [33].

Figure 4. CFD Geometry.
In Precision Ventilation, colliding jets are harnessed to establish distinct air velocity zones within open-plan offices, eliminating the necessity for partitions between individual workstations. When these jets collide, a downstream airflow is generated, which is subsequently employed to induce varying air speeds across different regions within the room. The intensity of the jet and the temperature of the supplied air contribute to a stronger downward airflow, resulting in elevated vertical air velocities.
Colliding jets with air velocities of 0.8 m/s and 0.6 m/s, respectively, are directed towards zones with metabolic rates of 1.6 MET and 1.4 MET. These colliding jets established different air velocity zones for different metabolic rate occupants to keep PMV-PPD values within acceptable limits [32].
Air velocities in the occupied zone were measured at 0.1 m and 1.1 m from the floor. Figure 5 shows the formation of air velocity zones suitable for occupants with different metabolic rates. The results illustrate four cases as an example of the studied Precision Ventilation technology.

Case 1: Conventional mixing ventilation with uniform air velocity distribution (0.15 m/s).

Case 2: Air velocity distribution (0.45 m/s) for two 1.4 MET occupants in Z-direction and air velocity distribution (0.15 m/s) for two 1.2 MET occupants in the other direction.

Case 3:Air velocity distribution (0.65 m/s) for a single 1.6 MET occupant in the ZX-direction and air velocity distribution (0.15 m/s) for three 1.2 MET occupants in the other directions.

Case 4: Air velocity distribution (0.65 m/s) for a single 1.6 MET occupant in the Z (-X)-direction, air velocity distribution (0.45 m/s) for a single 1.4 MET occupant in X (-Z)-direction and air velocity distribution (0.15 m/s) for two 1.2 MET in the other directions.
Figure 5. Variable air velocity Case 1, Case 2, Case 3, and Case 4. a=0.51 m above floor, b=1.1 m above floor.
By using precision ventilation during the cooling period, the annual energy savings from heating and cooling were 15% and this was achieved by raising the cooling setpoint by 2°C.
The following conclusions can be drawn from the above experimental and simulation study:
1. Precision ventilation can be based on a conventional mixed ventilation system using ACBs.
2. Precision ventilation can act as a new potential ventilation strategy to make the office environment more comfortable and productive for all office occupants.
3. JetCones instead of conventional nozzles brings a novelty in the application of ACBs, which simultaneously achieved low, medium and high-level air velocity zones in a shared office space.
4. The variation in local air velocities with respect to occupants’ metabolic rate and room air temperature significantly improved their thermal comfort.
5. Even the occupants with normal metabolic rates, seated together with occupants with higher metabolic rates that were seated in higher air velocity zones remained unaffected and were satisfied.
6. The annual energy savings of 15% were achieved by raising the cooling setpoint by 2°C.
[1] Frontczak, M., et al., Quantitative relationships between occupant satisfaction and satisfaction aspects of indoor environmental quality and building design. Indoor air, 2012. 22(2): p. 119-131.
[2] Roelofsen, P., The impact of office environments on employee performance: The design of the workplace as a strategy forproductivity enhancement. Journal of facilities Management, 2002. 1(3): p. 247-264.
[3] Brennan, A., J.S. Chugh, and T. Kline, Traditional versus open office design: A longitudinal field study. Environment and behavior, 2002. 34(3): p. 279-299.
[4] Al Horr, Y., et al., Occupant productivity and office indoor environment quality: A review of the literature. Building and environment, 2016. 105: p. 369-389.
[5] Indraganti, M. and K.D. Rao, Effect of age, gender, economic group and tenure on thermal comfort: A field study in residential buildings in hot and dry climate with seasonal variations. Energy and buildings, 2010. 42(3): p. 273-281.
[6] Li, G., C. Liu, and Y. He, The effect of thermal discomfort on human well-being, psychological response and performance. Science and Technology for the Built Environment, 2021. 27(7): p. 960-970.
[7] Olesen, B.W. and K. Parsons, Introduction to thermal comfort standards and to the proposed new version of EN ISO 7730. Energy and buildings, 2002. 34(6): p. 537-548.
[8] Lazzer, S., et al., Relationship between basal metabolic rate, gender, age, and body composition in 8,780 white obese subjects. Obesity, 2010. 18(1): p. 71-78.
[9] Kingma, B. and W. van Marken Lichtenbelt, Energy consumption in buildings and female thermal demand. Nature climate change, 2015. 5(12): p. 1054-1056.
[10] Rhee, K.-N., M.-S. Shin, and S.-H. Choi, Thermal uniformity in an open plan room with an active chilled beam system and conventional air distribution systems. Energy and Buildings, 2015. 93: p. 236-248.
[11] Veselý, M. and W. Zeiler, Personalized conditioning and its impact on thermal comfort and energy performance–A review. Renewable and Sustainable Energy Reviews, 2014. 34: p. 401-408.
[12] Arens, E., et al., A study of occupant cooling by personally controlled air movement. Energy and buildings, 1998. 27(1): p. 45-59.
[13] Latif, H., et al., Performance evaluation of active chilled beam systems for office buildings–A literature review. Sustainable Energy Technologies and Assessments, 2022. 52: p. 101999.
[14] Kaczmarczyk, J., A. Melikov, and P.O. Fanger, Human response to personalized ventilation and mixing ventilation. Indoor Air, 2004. 14: p. 17-29.
[15] Sekhar, S., et al., Findings of personalized ventilation studies in a hot and humid climate. HVAC&R Research, 2005. 11(4): p. 603-620.
[16] Zhang, H., et al., Comfort, perceived air quality, and work performance in a low-power task–ambient conditioning system. Building and Environment, 2010. 45(1): p. 29-39.
[17] Schiavon, S., A.K. Melikov, and C. Sekhar, Energy analysis of the personalized ventilation system in hot and humid climates. Energy and buildings, 2010. 42(5): p. 699-707.
[18] El-Fil, B., N. Ghaddar, and K. Ghali, Optimizing performance of ceiling-mounted personalized ventilation system assisted by chair fans: Assessment of thermal comfort and indoor air quality. Science and Technology for the Built Environment, 2016. 22(4): p. 412-430.
[19] Latif, H., et al. Design strategies for decreasing cooling demand and increasing individual thermal comfort in open-plan offices: A review. in 16th Conference of the International Society of Indoor Air Quality and Climate: Creative and Smart Solutions for Better Built Environments, Indoor Air 2020. 2020. International Society of Indoor Air Quality and Climate.
[20] Latif, H., et al., Precision Ventilation in an Open-Plan Office: A New Application of Active Chilled Beam (ACB) with a JetCone Feature. Sustainability, 2022. 14(7): p. 4242.
[21] Latif, H., et al., Precision Ventilation for an Open-Plan Office: A Study of Variable Jet Interaction between Two Active Chilled Beams. Sustainability, 2022. 14(18): p. 11466.
[22] Latif, H., et al., The establishment of design criteria for precision ventilation in open-plan offices. Building and Environment, 2023. 238: p. 110378.
[23] Melikov, A.K., Human body micro-environment: The benefits of controlling airflow interaction. Building and Environment, 2015. 91: p. 70-77.
[24] Latif, H., et al. Active Chilled Beams for Producing Symmetric Air Discharge Patterns Using Jet-Cone System: an experimental study. in Healthy Buildings 2021: America. 2021. International Society of Indoor Air Quality and Climate.
[25] Hoyt, T., E. Arens, and H. Zhang, Extending air temperature setpoints: Simulated energy savings and design considerations for new and retrofit buildings. Building and Environment, 2015. 88: p. 89-96.
[26] Rohles, F., The effects of air movement and temperature on the thermal sensations of sedentary man. ASHRAE transactions, 1974. 80: p. 101-119.
[27] Scheatzle, D., H. Wu, and J. Yellott, Extending the summer comfort envelope with ceiling fans in hot, arid climates. Ashrae Transactions, 1989. 95: p. 269-280.
[28] Gong, N., et al., The acceptable air velocity range for local air movement in the tropics. Hvac&r Research, 2006. 12(4): p. 1065-1076.
[29] Khedari, J., et al., Thailand ventilation comfort chart. Energy and buildings, 2000. 32(3): p. 245-249.
[30] Zhang, Y. and R. Zhao, Effect of local exposure on human responses. Building and Environment, 2007. 42(7): p. 2737-2745.
[31] ichi Tanabe, S. and K. ichi Kimura, Effects of air temperature, humidity, and air movement on thermal comfort under hot and humid conditions. ASHRAE transactions, 1994. 100(2): p. 953-969.
[32] Markov, D., Standards in thermal comfort. Annual International Course: Ventilation and Indoor Climate, Sofia, 2002: p. 147-157.
[33] Blocken, B. LES over RANS in building simulation for outdoor and indoor applications: A foregone conclusion? in Building Simulation. 2018. Springer.
Follow us on social media accounts to stay up to date with REHVA actualities
0