The Quality Management (QM) scheme was introduced in the 2005 regulation considering the difficulties building professionals had to achieve good airtightness and the hope that cost abatements due to allowance for non-systematic testing could encourage building professionals to engage in a QM approach (QMA) for building airtightness.
This scheme has become increasingly popular with the increased requirements in the regulation. In fact, the regulation now requires the justification of a given airtightness level for all residential buildings. This requirement was first experimented within the Effinergie label which was firmly based on the regulation. A similar approach is adopted for the Effinergie+ label with the aim to experiment possible changes for the next regulation update (see Figure 1). Justification of a given airtightness level can be provided either with a measurement by a certified tester or with a certified quality management approach.

Figure 1.Overview of building airtightness requirements in France.Airtightness values are in m³/h at 4 Pa per m² of cold area (excluding lowest floor).
The underlying idea of the QMA is to push professionals to get organized to properly design airtightness, to implement adequate solutions, to trace critical steps, and to monitor their performance. The QMA requirements detailed in the energy regulation are summarized in Figure 2. Applicants must propose a scheme to address each step listed in Figure 2 and to ensure that the approach will remain effective with time, based on measurements on a sample, by independent certified measurers. They also must have their system audited according to ISO 19011 (Guidelines for quality and/or environmental management systems auditing) by an independent ISO 9001 certified organisation.

Figure 2.Overview of requirements for a certified quality management approach.
After approval of their application by a committee of experts, successful applicants are not required to perform tests systematically but only on samples (typically 5% to 10% of their production for single-family dwellings with a third-party certified tester) to comply with the justification for the airtightness level used in energy performance calculation.
Despite legitimate concerns about its market penetration, its effectiveness, and its potential biases to competition, the current approach has proved to be successful among builders, to positively question applicants about their methods to reach good or at least required airtightness levels, and to be consistent with the achievement of better airtightness levels (Figure 3). The evaluation of the process conducted by the state authority has confirmed the effectiveness of the approach; it has also shown weaknesses that should be dealt with and strongly suggests reinforcing in situ controls to avoid deviations which may in turn question the relevance of the approach.

Figure 3.Distribution of measured airtightness of houses with and without implementation of a certified QM approach.
Additional information can be found in QUALICHeCK fact sheet #01
http://qualicheck-platform.eu/wp-content/uploads/2015/02/QUALICHeCK-Factsheet-01.pdf
![]()
QUALICHeCK responds to the challenges related to compliance of
Energy Performance Certificate (EPC) declarations and the quality of the
building works. Find out more at http://qualicheck-platform.eu.
The
QUALICHeCK project is co-funded by the Intelligent
Energy Europe Programme of the European Union. The sole responsibility for the
content of this article lies with the author(s). It does not necessarily
reflect the opinion of the European Union. Neither the EASME nor the European
Commission are responsible for any use that may be
made of the information contained therein.
Follow us on social media accounts to stay up to date with REHVA actualities
0