Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Risto KosonenProfessorAalto Universityristo.kosonen@aalto fi | Juha JokisaloD.Sc, senior scientistAalto Universityjuha.jokisalo@aalto.fi | Simo KilpeläinenD.Sc, laboratory managerAalto Universitysimo.kilpelainen@aalto.fi |
Demand response (DR) consist of a group of methods where the end-user’s energy load is modified to decrease the aggregated overall CO2 emissions of the energy production and to enhance the efficiency of the whole energy system. The end-user´s load may be shifted from expensive peak load periods to cheaper off-peak periods, the peak load may be cut, or extra load may be induced to off-peak periods. As a result, the aggregated load in the energy system will be stabilized and the demand for the fossil-fuel intensive peak-power plants will decrease.
While DR has been explored commonly for electricity grid, it has not been used commonly in district heating system. Earlier demand response studies have predominantly dealt with the electricity loads. However, there is a potential to save energy costs and reduce CO2 emission with district heating.
During the heating season, production cost
of the district heating power varies quite a lot. In Figure 1
shows an example of district
heating hourly price in Finland containing both energy and transfer costs (Salo et al. 2018). The prices remain stable during summer time (i.e. April to middle of
November (hours 2,100 – 7,900 in Figure 1) with an average value of 40.5 €/MWh
and a standard deviation of 7.7 €/MWh. During winter time, the
corresponding values are 68.0 €/MWh and 29.7 €/MWh.
Figure 1.
The dynamic district heating price of a typical producer in Finland.
Within DR controlled
space heating, loading is typically executed when the energy is cheap. The room air temperature is then increased to load heat
into the structures, which can be used during more expensive hours by lowering
the indoor air temperature setpoint.Figure 2 presents the principle of DR
control, where heating power is controlled by the known price trend (e.g. for
24 hours in advance).
Figure 2.
The principle of demand response control during changing price trend.
The control strategy itself could be rule-based or model-based. In the rule-based control algorithms studied at Aalto University, the decision-making was based on the outdoor and indoor air temperatures and the control signal generated from the dynamic price information (Martin 2018). Thestudied model predictive algorithms utilized sophisticated optimization algorithm (e.g. NSGA-II) where user can optimize contradictory functions e.g. energy costs and thermal comfort (Mäki 2019). However, based on the aforementioned studies, the saving potential of both rule-based and model-based control strategies is the same.
In an educational building, the simulated heat energy cost saving potential of DR with the dynamic district heating price (see Figure 1) is about 5% for a building owner, when room air temperature is accepted to vary between 20 – 24.5°C. At the same time, annual heating energy consumption decreased 3 to 5% in the studied building depending on the DR algorithm.
In the water radiator system, the heating power could be controlled at centralized or decentralized levels. Decentralized control refers to adjustments of mass flow of water radiators on room level (e.g. electronic radiator valve control), while centralized control refers to adjustments on system level (e.g. inlet water temperature control). By introducing room or zonal based decentralized control, it is possible to reach highest savings and decentralized control guarantee the set targets of thermal comfort in all rooms even when heat loads varied.
In the centralized DR control strategy, inlet water temperature of district heating system is adjusted based on the price signal. Based on the energy price trend, the controls have effect on the inlet water and further on room air temperatures. Centralized strategies were studied in one of the wings (13,800 m²) of a campus building at the Aalto University (Mistra et al. 2019). The goal was to examine how much deviations could be incurred in the inlet water temperature and how, if at all, that affected occupant perceptions.
The
building was refurbished in 2014 when ventilation, heating, and building
management systems were upgraded. The original 2-pane windows were renovated and
the renovated windows have a U-value of 1.0 W/m²K. The wing is equipped
with mechanical supply and exhaust ventilation system with regenerative heat
recovery. It is a variable air volume (VAV) system, controlling air flow rates
based on the dual inputs of room air temperature and carbon dioxide
concentration.
In testing
the DR scenarios, an inherent assumption was that dynamical pricing would be
available for district heating and a moving 24 hours, hourly price, would
be known in advance, at any point in time. The district heating price used in
the study is shown is Figure 1. The principle of the control
strategy used is as described in Figure 2.
During the
test, the heating water supplied to every radiator in the wing was altered,
where the maximum deviations of +11/−21°Cwere allowed for inlet water
temperature between actual and standard values (see Table 1). The minimum and maximum outdoor temperatures for each weekly period are
summarized in Table 1. The algorithm aimed at keeping
room air temperature within 20 – 24.5°C
To ensure
that all the occupied rooms kept within the required comfort zone, the
algorithms depended on the mean air temperature of the coldest and warmest
rooms. The coldest rooms were defined as rooms whose temperature was lower than
90% of the permanently occupied rooms of the wing and the warmest rooms were
defined as rooms whose temperature was higher than 90% of the permanently
occupied rooms in the wing. When mean air temperature of the coldest rooms fell
below 20°C, or mean air temperature in the warmest rooms rose over 24.5°C, the
standard control curve for inlet water temperature was used.
Table 1.
Ranges for outdoor temperature and heating water inlet temperature and
deviations during the weekly DR control periods.
P2 | P3 | P4 | P5 | P7 | P8 | P9 | P10 | P11 | P12 | P13 | |
Minimum outdoor temperature (°C) | 1.0 | 1.1 | −1.2 | −1.5 | 1.1 | 0.4 | −0.1 | −3.2 | −0.3 | −10.1 | −6.7 |
Maximum outdoor temperature (°C) | 12.5 | 15.3 | 7.3 | 6.2 | 7.0 | 7.5 | 7.5 | 6.0 | 5.8 | 6.2 | 5.3 |
Range of
deviation (°C) | −2.7 | −3.8 | −5.2 | −5.5 | −3 | −5.8 | −4.9 | −6.1 | −3.6 | −21.1 | −20.7 |
2.1 | 5.7 | 5.8 | 5.7 | 0.8 | 5.2 | 5.8 | 5.5 | 7.3 | 10.7 | 10.9 | |
Range of
inlet water temperature (°C) | 30.8 | 25.0 | 37.2 | 36.9 | 36.5 | 33.7 | 32.9 | 37.3 | 38.4 | 21.4 | 25.8 |
45.1 | 48.4 | 54.1 | 52.4 | 46.8 | 50.2 | 52.3 | 51.5 | 55.1 | 66.6 | 62.8 |
The
recorded room air temperature data covered all the rooms in one wing, where
some of these spaces were hallways, in the basement, housed
equipment/machineries etc. Excluding such rooms, which were not meant for
occupancy, left 115 rooms. The temperature data for these rooms was analyzed
together to provide a summary view of indoor thermal conditions during the
observation periods. Figure 3 provides the mean, minimum, and
maximum temperatures at each instant of record across all 13 weekly periods,
for the 115 rooms.
Figure 3 depicts that the maximum and
minimum temperatures show a broad range of variation. The current work was not
intended towards narrowing down to the causes of such variations but, some
possible reasons could be: higher/lower heat load than designed, balancing
problem of water network or too high/low airflow rate for demand in certain
spaces.
The results
for room indoor temperatures show that the mean temperature pattern during the
periods without DR control (P1 and P6) did not drastically deviate from the other
periods when the DR strategies were implemented.
Figure 3.
Summarized room air temperature conditions of the observed rooms.
During the
test periods, occupant acceptance on thermal comfort were collected (Table 2). Periods 12, and 13 fared particularly well with the occupants, each
securing over 70% positive feedback in spite of the fact that much larger
deviations in inlet water temperatures were allowed during these two periods.
It should
be noted that during certain periods of implementations, very few feedbacks
were received. However, based on the previous comfort studies, if the
perception on thermal comfort is very low level, people start to compline
anyhow. It seems so that it could be possible that the changes in the inlet
water temperature can be as high as +10/−20°C without sacrificing thermal
sensation of users. Because relatively low level of responses, more
measurements are required to confirm this conclusion.
Table 2.
Occupant acceptance on thermal comfort during different periods.
P1 | P2 | P3 | P4 | P5 | P6 | P7 | P8 | P9 | P10 | P11 | P12 | P13 | |
Number: | |||||||||||||
Negative | 8 | 11 | 1 | 1 | 3 | 2 | 55 | 35 | 54 | 61 | 46 | 13 | 5 |
Positive | 9 | 3 | 1 | 0 | 1 | 0 | 66 | 39 | 107 | 127 | 51 | 36 | 12 |
Percentage (%) | |||||||||||||
Negative | 47 | 79 | 50 | 100 | 75 | 100 | 45 | 47 | 34 | 32 | 47 | 27 | 29 |
Positive | 53 | 21 | 50 | 0 | 25 | 0 | 55 | 53 | 66 | 68 | 53 | 73 | 71 |
Based on simulations, demand response of
district heating in public buildings gives around 5% heating energy cost
savings, if room air
temperature is accepted to vary between 20 – 24.5°C. Using
centralized control strategy, the room air temperature of individual rooms is
not possible to control accurately. In the studied building, the temperature
variation is between 18 – 26°C in different rooms even demand
response is not introduced. That makes challenging to get full benefit of demand
response if there is no room or even zonal level decentralized control system. It
seems so that it could be possible to change inlet water temperature quite a
lot (about +10/−20°C) without users notice it. However, because
relatively low level of responded persons, more measurement is required to
confirm this conclusion.
The authors
are grateful for the funding provided by Business Finland for “Reino”, “Smart
ProHeat” and “Smart Otaniemi” projects. Special thanks to Aalto University
Properties (ACRE), Fidelix Oy, Granlund Oy and Fourdeg Oy for the assistance
with the measurements and the arrangement of the measurement setup.
Martin, K. (2017). Demand response
of heating and ventilation within educational office buildings; Master’s
Thesis. Aalto University. Espoo. http://urn.fi/URN:NBN:fi:aalto-201712187947.
Mishra, A. K., Jokisalo, J., Kosonen, R., Kinnunen, T., Ekkerhaugen, M., Ihasalo, H., & Martin, K. (2019). Demand response events in district heating: Results from field tests in a university building. Sustainable Cities and Society, 47, 101481. https://doi.org/10.1016/j.scs.2019.101481.
Mäki, A. (2018). Demand response of
space heating using model predictive control in an office building; Master’s
Thesis. Aalto University. Espoo. http://urn.fi/URN:NBN:fi:aalto-201812146470.
Salo, S., Hast, A., Jokisalo, J., Kosonen, R., Syri, S., Hirvonen, J., & Martin, K. (2019). The Impact of Optimal Demand Response Control and Thermal Energy Storage on a District Heating System. Energies, 12(9), 1678. https://doi.org/10.3390/en12091678.
Follow us on social media accounts to stay up to date with REHVA actualities
0