Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
|
|
Maria KolokotroniProfessor,Institute of Energy FuturesBrunel University London, UKmaria.kolokotroni@brunel.ac.uk | Thiago SantosPhD studentInstitute of Energy FuturesBrunel University London, UKthiago.santos@brunel.ac.uk | Nick HopperTechnical DirectorMonodraught Ltd, UKnick.hopper@monodraught.com |

Figure 1. Schematic of Cool-Phase system
with a graphical explanation of the PCM thermal battery principle of operation.
Thermal comfort evaluation is usually based
on current guidance on avoiding overheating in buildings. In the UK, current
guidance for schools is provided by the Education Funding Agency [1]; it
includes guidelines on ventilation, thermal comfort and indoor air quality,
including the Services Output Specification [2], the Baseline Design
Environmental Services and Ventilation Strategy [3] and the Building Bulletin
101 [4]. These documents are aligned with CIBSE's guidance on prevention of
summertime overheating [5,6 ,7 ,8] which refer to calculations according to European Standard BS EN 15251 and UK
Building Regulations Parts L (Conservation of Fuel and Power) and F
(Ventilation) [9].
Until recently overheating criteria for
schools were based on fixed air temperature (28°C which can be exceeded for 120 hrs
and 32°C not to be exceeded) outside the heating season and during the occupied
period from 1st May to 30th September.
Currently, the adaptive thermal comfort
approach is used which follows the methodology and recommendations of European
Standard EN 15251 to determine whether a building is overheated, or in the case
of an existing building whether it can be classed as overheating. The new
criteria are based on a variable (adaptive) temperature threshold that is
generated from the outside running-mean dry-bulb temperature. There are three
criteria, two of which must be met for compliance, as follows [3]:
(a) Hours of Exceedence: The number of hours operative temperature
exceeds the maximum acceptable operative temperature (θmax) by 1K, must
not exceed 3% of the total occupied hours or 40 hours, during the five summer
months.
(b) Weighted Exceedance: The sum of the weighted exceedance for each
degree K above θmax (1K, 2K and 3K) is ≤ 10.0.
(c) Threshold/Upper Limit Temperature (θupp): The
measured/predicted operative temperature should not exceed the θmax by 4K
or more at any time.
The case-study analysed in this paper was
built to comply with the older requirements so operational data are analysed
following both approaches.
In terms of IAQ based on CO2
concentration, until recently the guidance was that when measured at seated
head height, during the continuous period between the start and finish of
teaching on any day, the average concentration of carbon dioxide should not
exceed 1,500 parts per million (ppm). This criterion is changed to the
following criteria [3]:
(a) Ventilation should be provided to limit the concentration of
carbon dioxide measured at seated head height in all teaching and learning
spaces.
(b) Where mechanical ventilation is used or when hybrid systems are
operating in mechanical mode, i.e. the driving force is provided by a fan,
sufficient fresh air should be provided to achieve a daily average
concentration of carbon dioxide during the occupied period of less than 1,000 ppm
and so that the maximum concentration does not exceed 1,500ppm for more than 20
consecutive minutes each day.
The case-study is a seminar room at a university
campus in West England. Cool-Phase® systems have been installed in
other spaces of the university but the seminar room was chosen because of its
use (computer laboratory) with higher internal heat gains than other spaces.
The room has a floor area of 117 m² and includes 26 desk top computers,
peak occupancy of 26 students, and artificial lighting comprising of 24
luminaires each equipped with one 48 W lamp. The total internal heat gain
in the room is 60 W/m². The room has one external wall facing west with
U-value of 0.56 W/m² K while 23 % is glazing (U-value 1.82 W/m² K)
with internal blinds. Ventilation and cooling is provided via a 8 kW
Cool-Phase® unit. Heating is provided through perimeter hot water
radiators and windows are operable. Climate is temperate maritime with 2,684 Heating
Degree Days and 196 Cooling Degree Days; 20 year average, base 15.5°C, south
west England [10].
A Cool-Phase® system by
Monodraught Ltd was installed in May 2013 to provide ventilation for indoor air
quality and cool the air for thermal comfort. The Cool-Phase® system
uses the concept of a thermal battery consisting of Phase Change Material (PCM)
plates within the ventilation path to capture and store heat. Therefore, the
thermal batteries use the latent heat property of materials to store energy,
which is charged and discharged by passing air through a heat exchanger. A
diagram of the system is shown in Figure
1 where the principle of the PCM thermal battery
function is shown. The system is concealed in the false ceiling and its
appearance to the user is that of a conventional ventilation system with two
air supply terminals and one air extract terminal. Air is drawn from outside or
the room using a variable speed fan. During operational hours and depending on internal
air quality (monitored through CO2 sensors) the air is
mixed with recirculated air from the room to conserve energy. The air is then
directed through the PCM thermal battery to be cooled if necessary (determined
by air temperature sensors and control rules) or by-passes it if cooling is not
needed. Outside operational hours, ambient air is used to recharge the PCM
thermal battery the duration of which is determined by air temperature sensors
and control rules according to the season.

Figure 2. System operation over a summer
day in 2013.
Figure 2 shows how the system works based on monitored data during one day
in August 2013. The system starts with a charging-purge mode between midnight
and 1:00 and continues with charging mode from 1:00 to 7:00 am. Inlet and
outlet temperatures through the PCM thermal battery are decreasing with a
temperature difference between them indicating the battery is charging. The
system is off between 7:00 and 8:00 am when the cooling mode is initiated
and continues until 21:00. In the morning (8:00-~13:00) the temperature outside
the intake damper is lower than the set-point for summer (22°C) so the PCM
thermal battery is by-passed. At around 13:00, set-point temperature is
exceeded and the inlet air is directed to the PCM thermal battery through
recirculation. Inlet air is cooled to below room temperature until shortly
before 21:00 when the system is off until midnight. Maximum temperature in the
room is 24.5°C below max external temperature.

Figure 3. Thermal comfort performance over
the summer months.
Figure 3 shows temperatures in the case-study room during operational hours
in the summer of 2013 (May – September). According to adaptive thermal comfort
criteria, it can be observed that the system has achieved internal temperatures
within the upper and lower limits and therefore complies with all conditions. Also,
air temperatures do not exceed 28 or 32°C and daily average inside/outside
temperature difference is less than 5°C and therefore achieves comfort
according to static thermal comfort criteria.
An analysis of monitored room CO2 concentration was carried out for the whole year that data
are available. Table 1 presents the results. Daily average concentration during the
occupied period is always less than 1.000 ppm and the 1.500 ppm limit
was not exceeded with the exception of one occasion for 22 min when
occupancy was higher than designed and there was a conflict between IAQ and
thermal comfort.
Table 1. CO2
concentration (ppm): daily average and exceeding 1500 ppm for more than 20
consecutive minutes.
Month | Average | >1500ppm | Month | Average | >1500ppm |
May | 502 | 0 | November | 741 | 0 |
June | 423 | 0 | December | 566 | Once* |
July | 413 | 0 | January | 601 | 0 |
August | 416 | 0 | February | 719 | 0 |
September | 500 | 0 | March | 695 | 0 |
October | 595 | 0 | April | 579 | 0 |
*CO2 concentration
exceeded 1500 ppm for 22 min on mid-morning on 6 Dec 2013 when
occupancy in the room was more than its maximum and external air temperature at
~7°C. The control system restricted outside air to the room to less than
maximum capacity to avoid thermal comfort issues.
The fan energy used by the system for the
year was calculated to be 90 kWh. This equates to 0.77 kWh/m²/annum.
Annual electricity energy use intensity for secondary schools has a median of
51 kWh/m² [8]. This increases by 5 kWh/m² when moving from ‘heating
and natural ventilation’ to ‘heating and mechanical ventilation’ buildings. CIBSE
TM57 [8] presents good case-studies with cooling energy intensity of 12.5 kWh
and 3.5 kWh/m².

Figure 4. Air temperature and velocity in
two sections of the seminar room during the hour with highest internal
temperature (see Figure 3) and full occupancy and internal gains.
In the previous section average
environmental conditions in the room were reported. However, the distribution
is also important to examine whether there are areas within the room that
deviate from thermal comfort requirements. This was investigated using a CDF
model of the room. A 3D model of the room was constructed with summer boundary conditions;
the hour in July with the highest internal temperature was selected as the worst
case scenario and a steady state simulation was performed with full occupancy
and internal heat gains. Figure 4 shows the air temperature at 1.2 m height (student sitting
plane) and velocity fields at the plane of one air inlet. It can be observed
that air temperature is uniform across the room and there are no areas with
much higher air temperature which will cause discomfort. The air velocity
contours indicate that at occupancy level underneath the air inlet velocity is
in the range of 0.1–0.2 m/s with some small areas reaching 0.37 m/s Air
velocity is lower in the rest of the room. Changing the direction of inlet
louvres would reduce air velocities if this is required although higher
velocities might aid thermal comfort.
Analysis of one-year operational
environmental data for a seminar room equipped with a Cool-Phase®
system to provide cooling indicate that the system performs well throughout the
year in terms of IAQ and thermal comfort for an IT intensive seminar room. Further
analysis of a second year of operational data plus additional monitoring to
study the distribution of environmental conditions in the room and feedback by
users is under progress and will be reported in a case-study being developed
for EBC Annex 62.
[1] https://www.gov.uk/government/publications/acoustics-lighting-and-ventilation-in-schools/acoustics-lighting-and-ventilation-in-schools,
assessed 07/08/2015.
[2] EFA,
Services Output Specification, June 2013;
https://www.gov.uk/government/publications/psbp-facilities-and-services-output-specifications;
assessed 07/08/2015.
[3] EFA,
Baseline Designs for Schools, 'Environmental Services Strategy' and
'Ventilation Strategy', March 2014,
https://www.gov.uk/government/publications/psbp-baseline-designs; assessed
07/08/2015.
[4] Building
Bulletin 101, Ventilation of School Buildings, July 2006.
https://www.gov.uk/government/publications/building-bulletin-101-ventilation-for-school-buildings;
assessed 07/08/2015.
[5] CIBSE
Guide A, Environmental Design, Chapter 1 Environmental Criteria for Design,
Eighth edition March 2015.
[6] CIBSE
TM52. The limits of thermal comfort: avoiding overheating in European
buildings, July 2013.
[7] CIBSE
KS16. How to manage overheating in buildings: A practical guide to improving
summertime comfort in buildings, July 2010.
[8] CIBSE,
TM57, Integrated School Design, April 2015.
[9] http://www.planningportal.gov.uk/buildingregulations/approveddocuments/;
assessed 07/08/2015.
[10] http://www.vesma.com/;
assessed 10/08/2015.
Follow us on social media accounts to stay up to date with REHVA actualities
0